ICH Stability Rooms Without the Long Lead Times
Faster Timelines.
Proven Performance.
The Darwin Chambers pre-engineered walk-in stability rooms are designed to reduce project timelines, simplify installation, and save up to 30% compared to fully custom-engineered solutions. Delivering precise temperature and humidity control that exceeds ICH performance requirements, it’s an ideal solution for regulated environments requiring dependable environmental storage.
Built Around Proven Stability Conditions.
Rather than beginning every project from scratch, these stability rooms have been engineered around one of the most requested ICH stability room configurations.
Standard Environmental Conditions
- 25°C to 40°C temperature range
- 60%RH to 75%RH humidity range
- Temperature control at sensor/set point: ±0.2°C
- Humidity control at sensor: ±0.3%RH
Demonstrated Performance
Performance mapping of similar installations has repeatedly documented environmental uniformity better than ±0.4°C and ±0.7%RH throughout the storage space over a 24-hour period. Documentation demonstrating performance exceeding ICH guidelines is available upon request.
Delivered. Installed. Commissioned.
From manufacturing through startup, our team manages the process to help get your stability program up and running faster.
Professional Installation
Freight Included
Startup and Commissioning
Every room undergoes startup and commissioning procedures to verify proper operation before being placed into service.
Factory-Tested Components
NIST-Traceable Instrumentation
Calibration Documentation
IQ/OQ/PQ Services Available
Qualification services are available through our factory-trained service team to help support validation requirements and accelerate deployment.
Designed for Reliable Environmental Performance
Proprietary Ultrasonic Humidification
Continuous Refrigeration Design
NIST-Traceable Calibration
Sustainable Panel Construction
Need refrigerated, cold storage instead?
Introducing Pre-engineered Cold Rooms
Not every project requires controlled humidity or ICH stability testing.
Darwin Chambers pre-engineered cold rooms deliver the same advantages of our pre-engineered stability rooms, including expedited installation timelines, high-quality precision construction, and dependable environmental performance for refrigerated storage applications.
Standard Environmental Conditions
- Temperature range: 2°C to 8°C
- Temperature control at sensor: ±0.2°C
- Designed for operation in controlled ambient conditions of 22.2°C ±4.4°C and a dew point at or below 11.1°C (22.2°C / 50% RH)Designed for operation in controlled ambient conditions of 22.2°C ±4.4°C and a dew point at or below 11.1°C (22.2°C / 50% RH)
Included Features
- Freight included*
- Professional installation
- Startup and commissioning
- NIST-traceable calibration
- Factory-tested components
- Proven modular construction
See What's Included. Before It's Installed.
Technical Specifications & Additional Details
Chamber Operation & Environmental Performance
These rooms are designed to deliver precise and repeatable environmental conditions for regulated stability testing applications.
Chamber Operation
- Model Number: ICH-G1HD-10X10
- Chamber Temperature Range: 25°C to 40°C
- Chamber Temperature Control at Sensor/Set Point: ±0.2°C
- Chamber Relative Humidity Range: 60%RH to 75%RH
- Chamber Humidity Control at Sensor: ±0.3%RH
Temperature and relative humidity specifications assume standard operation in a controlled ambient environment of 72°F ±8°F and a dew point at or below 50°F.
Demonstrated Environmental Performance
Performance mapping of similar installations, conducted using 24 Type “T” thermocouples and 8 Rotronic HygroClip sensors in conjunction with a Kaye 2000 Validator, has repeatedly documented environmental uniformity better than:
- ±0.4°C temperature variance
- ±0.7%RH humidity variance
These measurements were recorded throughout the storage space over a 24-hour period. Documentation demonstrating performance exceeding ICH guidelines is available upon request.
Cold Room Operation & Environmental Performance
The Cold Room Special is designed to deliver precise refrigerated storage conditions for regulated pharmaceutical, laboratory, and research applications.
Chamber Operation
- Model Number: LAB-G1NN-10X10
- Chamber Temperature Range: 2°C to 8°C
- Chamber Temperature Control at Sensor: ±0.2°C
Cold Room Operating Conditions & Performance Notes
Performance specifications assume standard loading, adequate airflow, and operation in a controlled ambient environment of 22.2°C ±4.4°C with a dew point at or below 11.1°C (22.2°C / 50% RH). Extended operation at some set points below 4°C may require slight defrost tolerances.
Standard Chamber Specifications
These rooms are built around one of our most requested walk-in stability room configurations to simplify project planning and accelerate installation timelines.
| Specification | Details |
|---|---|
| Exterior Dimensions | 10′ W x 10′ L x 8- 5 3/4″ H |
| Temperature Range | 25°C to 40°C |
| Humidity Range | 60%RH to 75%RH |
| Door Size | 36″ Keyed Entry Door |
| Floor Construction | 2 3/4″ Insulated Smooth Aluminum |
| Lighting | Vapor-Proof LED Lighting |
| Chamber Configuration | Walk-In Stability Room |
Chamber Construction Details
Designed for durability, thermal efficiency, and long-term environmental performance.
Modular Panel Construction
- 100% poured-in-place polyurethane insulated modular panels
- R-Value 31+
- 4″ insulated walls and ceiling
- Ecomate® polyurethane insulation technology
Sustainable Design
These rooms utilize Ecomate® polyurethane insulation, delivering:
- Zero Global Warming Potential
- Zero VOC emissions
- Exceptional thermal efficiency
Surface Finishes
| Surface | Finish |
|---|---|
| Interior | Embossed White Aluminum |
| Exterior | Embossed white Galvalume |
Floor Construction
- Floor Thickness: 2 3/4″
- Floor Finish: Smooth aluminum surface
Controls & Instrumentation
Reliable environmental control begins with proven instrumentation and industry-trusted components.
Included Controls
- Fuji PID / Fuzzy Logic Microprocessors for temperature and humidity control
- Dual display of actual and set point temperature
- Solid-state control relays wherever possible
- Controls mounted within an automation control panel per customer instruction
Instrumentation
- NIST-traceable 100 OHM Platinum RTD temperature sensor
- Calibration certificate included
Alarm Functions
High and low alarms are included for:
- Temperature
- Relative humidity
Additional features include:
- Dry contact remote alarm output
- Alarm settings configurable in 0.1°C and 0.1%RH increments
Mechanical Components
These rooms are engineered using proven technologies designed to promote environmental uniformity and dependable chamber operation.
Refrigeration System
- Top-mounted condensing unit
- Designed for continuous operation to promote superior temperature control and uniformity
- Eliminates many of the performance limitations inherent in cycling-type refrigeration systems
Air Handler
- Low-profile evaporator and air handling system
Humidification System
Darwin Chambers’ proprietary ultrasonic humidification technology provides:
- Precise humidity control
- Improved environmental uniformity
- UV disinfection capabilities
Desiccant Dryer
- Electric heat regenerating desiccant wheel dryer mounted above the chamber
Lighting
- Vapor-proof LED lighting for safe and reliable chamber illumination
What's Included
These rooms are designed to simplify deployment and accelerate project timelines.
Included with every pre-engineered stability room:
- Freight to the jobsite
- Professional installation by Darwin Chambers
- Startup and commissioning services
- Chamber documentation
- NIST-traceable calibration documentation
- Factory-trained service support
- IQ/OQ/PQ services available upon request
Installation Requirements
To help ensure a successful installation, customers are responsible for the following items unless otherwise specified:
- Taxes, licenses, permits, and associated fees
- Third-party labor requirements
- Bonds, if required
- Site preparation activities
- Potential hoisting or egress requirements to the installation location
- Final electrical connections to customer-supplied fused disconnects
- Final water and drain connections
Our team is available to discuss installation requirements during the project planning process.
Quote Conditions
Pricing for these pre-engineered stability rooms is based upon:
- Typical installation within 1,000 miles of the Darwin Chambers manufacturing facility (additional distances may affect pricing)
- Factory installation
- Unconditional jobsite access
- Specifications and assumptions outlined within the project quotation
Darwin Chambers reserves the right to adjust pricing or project scope prior to sale. All projects are subject to Darwin Chambers’ standard Terms and Conditions of Sale.
The Darwin Advantage
Every Darwin Chambers environmental chamber is backed by decades of engineering expertise and a commitment to delivering reliable environmental performance.
NIST-Traceable Calibration
All installed instrumentation is calibrated to NIST-traceable standards and provided with accompanying calibration documentation.
Factory Calibration
Our in-house calibration process utilizes state-of-the-art equipment and includes:
- Three-point calibration verification
- Traceable calibration documentation
- Factory-tested instrumentation
Proven Environmental Performance
These rooms are built upon a proven walk-in stability room configuration that delivers exceptional environmental control and uniformity for regulated applications.
Downloads & Documentation
Additional technical resources are available upon request.
- Pre-engineerd Stability Room Specification Sheet (PDF)
- Chamber Utility Requirements
- Installation Documentation
- Calibration Documentation
- Chamber Layout Drawings
- Environmental Performance Documentation
- Product Brochure
- ICH Performance Documentation
Need additional technical information? Our engineering team is available to discuss your environmental requirements and chamber specifications.
Ready to accelerate your next environmental room project?
Whether you require a walk-in stability room or refrigerated cold room, our pre-engineered solutions are designed to reduce costs, accelerate installation, and deliver dependable environmental performance.
Phone
(314) 534-3111
Email
sales@darwinchambers.com